The surge arresters commonly defined as SPDs (Surge Protection Devices), are devices designed to protect electric systems and equipment against transient and impulse overvoltages such as those caused by lightning strikes and by electric switching.
Their function is to divert the discharge or impulse current generated by an overvoltage to earth/ground, thereby protecting the equipment downstream.
SPDs are installed in parallel with the electric line to be protected. At the mains rated voltage, they are comparable to an open circuit and have a high impedance at their ends.
In the presence of an overvoltage, this impedance falls to very low values, closing the circuit to earth/ground.
Once the overvoltage has ended, their impedance rises again rapidly to the initial value (very high), returning to open loop conditions.
The Type1+ 2 SPD is the main protection system for all low voltage electrical installations. Installed in each electrical switchboard, it prevents the spread of overvoltages in the electrical installations and protects the loads.
Type1+ 2 surge protective devices (SPDs) are designed to protect electric installations and sensitive equipment against indirect surges and ensuring a low protection level (Up).
Type 2 surge protective devices provide effective protection against these dynamic disturbance variables. Whether in an industrial environment or in a residential building, type 2 protection ensures basic protection for your installations and devices.
The B+C series type 1+2 SPDs are available have a discharge capacity of 10kA, 20KA, 40KA, 60KA in single-phase or 3-phase configuration and with various voltages in order to protect any type of power supply system.
THOR Type 1+2 DIN-rail SPD features are offering quick thermal response and perfect cut-off function and providing fast and reliable protection for various power supply systems.And its capacity to safely discharge current with 8/20 μs waveform.
Built with window fault indication and optional remote alarm contact, it can monitor the operating status of the SPD itself.
Parameter/Type | TRS30B+C |
Nominal volatge Un | 230 V AC |
Maximum operating voltage Uc | 275 V AC |
Lightning impulse current (10/350 μs) Iimp | 7 kA |
Nominal discharge current (8/20μs) In | 30 kA |
Maximum discharge current (8/20μs) Imax | 60 kA |
Voltage protection level Up | ≤ 01,5 kV |
Response time ta | < 25ns |
Cross-section of connected conductors solid (min/max) | 16 mm2 / 35 mm2 |
Cross-section of connected conductors stranded (min/max) | 16 mm2 / 35 mm2 |
Fault indication | red indication field |
Remote indication | potential-free change-over contact |
Remote indication contacts | 250 V / 0,5 A AC, 250 V / 0,1 A DC |
Cross-section of remote indication conductors | 1,5 mm2 |
Degree of protection | IP20 |
Range of operating temperatures (min/max) | -40℃~+70℃ |
Humidity range | 5%~95% |
Humidity range | DIN rail 35 mm |
According to standard | EN 61643-11:2012, IEC 61643-11:2011 / T2 |
Remarks | Other Uc can be customized.(420V AC, 385V AC, 320V AC, etc.) |