The surge arresters commonly defined as SPDs (Surge Protection Devices), are devices designed to protect electric systems and equipment against transient and impulse overvoltages such as those caused by lightning strikes and by electric switching.
Their function is to divert the discharge or impulse current generated by an overvoltage to earth/ground, thereby protecting the equipment downstream.
SPDs are installed in parallel with the electric line to be protected. At the mains rated voltage, they are comparable to an open circuit and have a high impedance at their ends.
In the presence of an overvoltage, this impedance falls to very low values, closing the circuit to earth/ground.
Once the overvoltage has ended, their impedance rises again rapidly to the initial value (very high), returning to open loop conditions.
The first-level lightning protection device can discharge the direct lightning current, or discharge the huge energy conducted when the power transmission line is directly struck by lightning. For places where direct lightning strikes may occur, CLASS-I lightning protection must be carried out.
The TRS-A series type 1 SPDs are available have a impulse current capacity of 15kA, 25KA, 50KA in single-phase or 3-phase configuration and with various voltages in order to protect any type of power supply system.
THOR Type 1 DIN-rail SPD features are offering quick thermal response and perfect cut-off function and providing fast and reliable protection for various power supply systems.And its capacity to safely discharge current with 10/350 μs waveform.
Parameter/Type | TRS-A15 | TRS-A25 | TRS-A50 |
Nominal volatge Un | 230 V AC | ||
Maximum operating voltage Uc | 275 V AC | ||
Lightning impulse current (10/350 μs) Iimp | 15 kA | 25 kA | 50 kA |
Voltage protection level Up | ≤ 2,0 kV | ≤ 2,2 kV | ≤ 2,5 kV |
Insulation resistance group | > 100 mΩ | ||
Response time | <100ns | ||
Cross-section of connected conductors solid (min/max) | 16 mm2 / 35 mm2 | ||
Cross-section of connected conductors stranded (min/max) | 16 mm2 / 35 mm2 | ||
Fault indication | — | ||
Degree of protection | IP20 | ||
Range of operating temperatures (min/max) | -40℃~+70℃ | ||
Humidity range | 5%~95% | ||
Mounting | DIN rail 35 mm | ||
According to standard | EN 61643-11:2012, IEC 61643-11:2011 / T1 | ||
Remarks | Other Uc can be customized.(420V AC, 385V AC, 320V AC, etc.) |