Tubo de descarga de gás cerâmico
Tubo de descarga de gás cerâmico is the most widely used switching device in lightning protection equipment. Gas discharge tube (GDT) uses metallized ceramic tubes and two or more electrodes to seal one or more discharge gaps. Inert gas is filled inside the ceramic gas discharge tube, and active electron powder is coated on the effective electron emission surface of the electrodes. The distance between electrodes less than 1mm can ensure the stability of the breakdown voltage of the discharge tube. The ceramic gas discharge tube is cylindrical in shape and has two structural forms with and without leads. Tubo de descarga de gás cerâmicos are used in communication or signal circuits with AC not exceeding 1200V and DC not exceeding 1500V, especially in the protection of information and signal systems. The tube is filled with an inert gas with stable electrical properties, such as argon and neon.
A figura a seguir mostra os símbolos do circuito do tubo de descarga de gás sob diferentes condições.
Quando a tensão no tubo de descarga de gás atinge a tensão de descarga CC, o gás interno se decompõe e é descarregado. A característica volt-ampere do tubo de descarga de gás é não linear e o processo de ruptura é dividido em três estágios: a resistência DC permanece acima de 10°Ω antes da ruptura; a impedância e a queda de tensão do tubo caem drasticamente no momento da ruptura, e a corrente de condução é severa. A impedância e a queda de tensão do tubo permanecem em um nível muito baixo imediatamente após a quebra e continuam até que a tensão na linha seja inferior à tensão do arco do tubo de descarga de gás e, em seguida, retornem ao estado de circuito aberto por si só.
símbolo do circuito do tubo de descarga de gás